LZB35 buffer power supply
Application
LZB35-1215 buffer power supply is destined to supply various kinds of devices and systems with the voltage of 12V (1215 model) and 24V (2408 model). Buffer working system of a power supply consists in a parallel connection of an accumulator's power supply on output terminals, for which the producer allows the output charging current 15A. At the basic power supply of 230V AC the power supply provides receivers with energy and, simultaneously, charges a connected accumulator with voltage compressed by means of temperature. Consequently, output voltage of a power supply during buffer work depends on the temperature of a temperature probe, which should be attached to an accumulator.
A power supply can also work as a source of a normal DC voltage of a high stabilization factor with a possibility of setting output voltage around 11-15V (1215 model, 1215W) and 22-30V (2408 model.) In such a case a temperature probe should be replaced by 680 Ohm resistor. LZB35 power supply can be connected in series or in parallel and in a connection with LFP32 inverter it can be used as a long-time power supply device, depending on the capacity of the accumulator batteries.
Construction
LZB35 power supply is an high-efficient PWM converter, that has short-circuit and overload protection. It is also equipped with a signalization system (LEDs and signalization relay's terminals), that gives information about accumulator's state. The converter has a build-in temperature protection that stops the converter if a surrounding air temperature exceeds 80oC - when the temperature diminishes, the converter goes back to normal work. In “W” power supply, there is a built-in module measuring voltage and output current.
Specifications
|
AC power supply:
|
190÷240V 300 W (system limiting OUTPUT?? current of a converter to 4A) |
|
Output voltage:
1215 model
|
1115VDC (factory settings 13,8V * at 20C)
|
|
2408 model Maximum output power:
|
2230VDC (factory settings 27,6V * at 20C) 250W*
|
|
Limit for the output current:
1215 model
2408 model
|
15÷17,5A*
8÷9A*
|
|
Efficiency:
|
82%
|
|
230V terminals' protection:
|
semiconducting varistors 600V
|
|
Optical signalling:
|
“SIEĆ 230V AC” LED shines – the presence of 230V voltage on L and N terminals „Uacu>10,5V” or „Uacu>21V” LED shines – output voltage of the power supply over 10.5V or 21V (both when the accumulator is connected and disconnected) depending on the model of the power supply |
|
Signalling transmitters
|
The terminals of two switching relays, which armature's state changes adequately to the change of signalling “PRACA” LED and „Uacu>10,5V” or „Uacu>21”. The state of normal work (230V AC net connected, accumulator connected, output voltage of the power supply >10.5V or >21V accordingly) – all the LEDs shine, contacts 1 and 2 of PA and PB relays short - -circuited. |
|
Measure (realization W)
|
LED display, the measurement of voltage exact to 100mA
|
|
Weight
|
2.4kg
|
|
Dimensions
|
166x87x300mm
|
|
Cage:
|
steel, powder-painted or galvanized
|
|
Terminals - functions
|
+,- - output voltage (all the terminals marked with “+” are short-circuited, all the terminals marked with “-” are short-circuited |
|
Terminals – electrical data
|
A single terminal – 2.5mm2 lead, 10A (12A) load
|
|
* in case of a temperature probe connected to the accumulator the voltage can be changed in temperature function, according to the characteristics recommended by the producers of accumulators – compare with the voltage- current- temperature-characteristics of the power supply |
|
![LEP [PL]](http://lep.pl/design/lep/pl.gif)